Section
Number
Name
Description
Size
Flags
CLIMATE SPECIFIC
PAGES
156-159
[Climate x] Fan Indicator
Fan Level (as parameterized)
1 byte
W
160-163
[Climate x] Binary 1 Indicator
0=Off; 1=On
1 bit
W
164-167
[Climate x] Binary 2 Indicator
0=Off; 1=On
1 bit
W
168-171
[Climate x] Special Mode Indicator
Comfort, Standby, Economy and
Building Protection
1 byte
W
ALARMS
172-179
[Alarms Box y] Alarm
Trigger
1 bit
W
180-187
[Alarms Box y] Confirmation
0=No action; 1=Confirm
1 bit
WT
THERMOSTAT 1
188
[T1] Temperature Source 1
External sensor measure
2 byte
W
189
[T1] Temperature Source 2
External sensor measure
2 byte
W
190
[T1] Special Mode
1-byte HVAC mode
1 byte
W
191
[T1] Special Mode: Comfort
0=Nothing; 1=Trigger
1 bit
W
0=Off; 1=On
192
[T1] Special Mode: Standby
0=Nothing; 1=Trigger
1 bit
W
0=Off; 1=On
193
[T1] Special Mode: Economy
0=Nothing; 1=Trigger
1 bit
W
0=Off; 1=On
194
[T1] Special Mode: Protection
0=Nothing; 1=Trigger
1 bit
W
0=Off; 1=On
195
[T1] Window Status (input)
0=Closed; 1=Open
1 bit
W
196
[T1] Comfort Prolongation
0=Nothing; 1=Timed Comfort
1 bit
W
197
[T1] Special Mode Status
1-byte HVAC mode
1 byte
RT
198
[T1] Setpoint
Thermostat setpoint input
2 byte
W
[T1] Basic Setpoint
Reference setpoint
2 byte
W
199
[T1] Setpoint Step
0=-0.5ºC; 1=+0.5ºC
1 bit
W
200
[T1] Setpoint Offset
Float offset value
2 byte
W
201
[T1] Setpoint Status
Current setpoint
2 byte
RT
202
[T1] Basic Setpoint Status
Current basic setpoint
2 byte
RT
203
[T1] Setpoint Offset Status
Current setpoint offset
2 byte
RT