ZENNiO AVANCE Y TECNOLOGÍA _vwww.zennio.com
The shutter control operates as follows:
Short press: On a short press of the left button, the value "1" will be sent via the
object "[Home x - Box y] Stop Shutter", thus making the shutter stop. On a short press of
the right button, the value "0" will be sent via the same object and this will also stop the
shutter. If the shutter is already stationary, a short press will have no action.
Long press: If the left button is long-pressed, the value "1" will be sent through the
object "[Home x - Box y] Move Shutter", thus making the shutter move down, until it
completes its length or until receiving a stop order via the corresponding object. If the
right button is long-pressed, the value "0" will be sent via the object "[Home x - Box y]
Move Shutter", thus making the shutter move up, until it completes its length or until
receiving a stop order via the corresponding object.
The object "[Home x - Box y] Shutter Position" must be linked, with the same group address,
to a status object that shows the current position (in percentage) of the shutter to control, in
order to update the percentage indicator that appears in the centre of the box with the current
shutter position.
Note: The value 0% indicates that the shutter is completely up, whereas the value 100%
indicates that the shutter is completely down.